SPECIFICATIONS DATA AIR COOLED CHILLER UNIT
No. DETAIL DESCRIPTION
1 MODEL           CU / CH 1260    
2 CAPACITY BTU/Hr   1,260,000  
3 UNIT POWER INPUT KW         142    
4 UNIT DIMENSION mm.(W x D x H)   2286 x 5300 x 2055  
5 UNIT WEIGHT KGS         SHIPPING WT = 3300 KGS    
        OPERATING WT = 3566 KGS    
6 CONTROL SYSTEM TYPE   MICRO COMPUTER CONTROL  
  WITH LCD DISPLAY  
7 COMPRESSOR Q'TY         8    
8 TYPE         HERMATIC SCROLL    
9 POWER INPUT ( KW)       16    
10 BRAND   COPE LAND  
11 MODEL         ZR19M3TWD    
12 COOLER Q'TY         1    
13 TYPE   SHELL AND TUBE  
14 BRAND         ALFA LAVAL    
15 MODEL   DXQ345 / STD  
16 # REFRIG CIRCUIT       4    
17 EVAP TEMP   1° C  
18 CHILLED WATER IN / OUT     12 ° C / 7° C     
19 CHILLED WATER FLOW   17.7 L/S  
  CHILLED WATER PD       7.2 PSI    
20 NOZZLE CONNECTION   IN = 5" / OUT = 5"  
21 CONDENSER  Q'TY         1    
22 TYPE   AIR COOLED CU TUBE , AL FIN  
  TOTAL AIR FLOW       128,500 CMH    
23 BRAND   CI GROUP  
24 # REFRIG CIRCUIT       4    
25 AMBIENT TEMP   35° C  
26 CONDENSING TEMP       50° C    
27 # FAN    8 x 28"  
28 FAN POWER (EACH)       3 / 4 HP   220V/1Ph/50-60Hz